After water flow is activated at the shower or eyewash, the outlet water temperature will reach 85°F (29°C) when hot water arrives at the mixing valve. The mixing valve then blends the hot and cold water to produce an output of 85°F (29°C) water.
OSHA and ANSI require all your emergency fixtures to provide tepid water for a minimum & continuous 15-minute cycle. Tepid is defined to be between 60°F (16°C) and 100°F (38°C). The Therm-O-Mix® WWM Tepid Delivery System can ensure your emergency equipment will meet these codes. Since the station does not require any electric power, it is suitable for explosion-proof environments and outdoor installations.The Therm-O-Mix WWM tepid water mixing valve is typically used in facilities with only hot and cold water supply to provide tepid water delivery to safety shower and face/eyewash stations.
- Cv = 10.0 Conforms to OSHA and ANSI recommendations
- Provides 85°F (29°C) tepid water from 3 GPM (11.4 L/min) to 25 GPM (113.7 L/min) with water inlet pressure of at least 40 PSIG (2.8 BAR)
- Compact, lightweight (under 15 lbs/6 kg) design easily supported by piping connections
- All components are in-line serviceable
- Easy to retrofit on existing shower or combination shower/eyewash stations
- Maintains constant 85°F (29°C) output
- All self-operating controllers - no power required
- Utilizes existing hot and cold water supply
- Optional durable, all weather version in high visibility LDPE enclosure available
| Series | Therm-O-Mix® Station WWM |
| Description | THERM-O-MIX® STATION/WWM-85°F |
| Cv | 10 |
| Weight | 15 lbs (6 kg) |
| Outlet Flow Rate Max | 25 GPM (113.7 L/min) |
| Outlet Flow Rate Min | 3 GPM (11.4 L/min) |
| Minimum Inlet Water Pressure | 40 PSIG (2.8 BAR) |
| Outlet Temperature | 85°F (29°C) |
| Isometric View | Download |
| Front View | Download |
| Top View | Download |
| Side View | Download |
Disclaimer
All drawings and 3D models are provided for reference only and are not controlled documents. Files may not reflect current revisions or design intent and shall not be used for manufacturing, inspection, or certification. Only officially released ThermOmegaTech drawings and documents issued through the company’s controlled document system are considered authoritative.
All drawings and 3D models are provided for reference only and are not controlled documents. Files may not reflect current revisions or design intent and shall not be used for manufacturing, inspection, or certification. Only officially released ThermOmegaTech drawings and documents issued through the company’s controlled document system are considered authoritative.
.png)